Airport Cable  

   Indoor Feeder Cables

600/1000V XLPE Insulated, LSZH Sheathed, Armoured Power Cables (Single Core)
FTX300 1RZ1MZ1-R (CU/XLPE/LSZH/AWA/LSZH 600/1000V Class 2)

APPLICATION
The cables is mainly used in power stations, mass transit underground passenger systems, airports,
petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design to BS 6724
FIRE PERFORMANCE

FlameRetardance (SingleVerticalWireTest)

EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2);

CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced FirePropagation(Vertically-mountedbundledwires

&cabletest)

EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI20-37/2-1;BS6425-1*

NoCorrosive GasEmission

IEC60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI20-37/2-2;BS6425-2*

MinimumSmokeEmission

IEC61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI20-37/3-1&2; EN50268-1&2*;BS 7622-1&2*

NoToxic Gases

NES02-713;NF C 20-454

Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000V

CABLE CONSTRUCTION
Conductor : Plain annealed copper wire, stranded according to IEC 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner sheath : LSZH Compound
Armouring : Aluminium Wire
Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.
COLOUR CODE
Insulation Colour : Natural
Sheath Colour : Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature Range During Operation: -30°C ~ 90°C
Temperature Range during Installation : -5°C ~ 50°C
Minimum Bending Radius: 8 x OD
Electrical PROPERTIES

DielectricTest:

3500 Vr.m.s.x 5’(core/core)

Insulation Resistance

500 MΩ x km ( at 20°C )

ShortcircuitTemperature

250°C ( up to5secs)

CONSTRUCTION PARAMETERS

 

 

 

Cable
Code

Conductor

 

 

Diameter
Under
Armour

 

 

Armour Wire Diameter

 

 

Nominal
Overall Diameter

 

 

 

Approx. Weight

No. of CoreX

Cross
Section

No. /Nominal
Diameter
of
Strands

 

mm2

No./mm

mm

mm

mm

kg/km

FTX300 1RZ1MZ1-R1G70

1x70

19/2.14

15.4

1.25

21.5

960

FTX300 1RZ1MZ1-R1G95

1x95

19/2.52

17.3

1.25

23.4

1240

FTX300 1RZ1MZ1-R1G120

1x120

37/2.03

19.1

1.6

25.9

1650

FTX300 1RZ1MZ1-R1G150

1x150

37/2.25

21.1

1.6

27.9

1970

FTX300 1RZ1MZ1-R1G185

1x185

37/2.52

23.2

1.6

30.1

2390

FTX300 1RZ1MZ1-R1G240

1x240

61/2.25

26.2

1.6

33.2

3040

FTX300 1RZ1MZ1-R1G300

1x300

61/2.52

28.8

1.6

35.8

3790

FTX300 1RZ1MZ1-R1G400

1x400

61/2.85

32.7

2.0

40.9

4790

FTX300 1RZ1MZ1-R1G500

1x500

61/3.20

36.2

2.0

44.6

5880

FTX300 1RZ1MZ1-R1G630

1x630

127/2.52

40.6

2.0

49.2

7400

FTX300 1RZ1MZ1-R1G800

1x800

127/2.85

45.7

2.5

55.7

9500

FTX300 1RZ1MZ1-R1G1000

1x1000

127/3.20

50.6

2.5

61.0

11750

Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)

 

Conductor
cross- sectional area

 

Reference Method1
(clipped

direct)

 

Reference
Method11(ona perforated

horizontal
cable
trayor
Reference
Method 13
[freeair])

 

 

Reference
Method 12(free air)

 

 

 

Insingle-
wayducts

 

 

 

Laiddirectin
ground

 

 

2

cables, single- phase

a.c.ord.c.

 

 

3 or 4cables, 3-phasea.c.

 

2

cables, single- phase

a.c.ord.c.

 

 

3 or 4cables, 3-phasea.c.

 

 

3cables 3-phase

a.c.trefoiltouching

 

2

cables, single- phase

a.c.ord.c.

 

 

3 or 4cables, 3-phasea.c.

 

2

cables, single- phase

a.c.ord.c.

 

 

3 or 4cables, 3-phasea.c.

1

2

3

4

5

6

7

8

9

10

mm2

A

A

A

A

A

A

A

A

A

70

303

277

322

293

285

310

280

340

290

95

367

333

389

352

346

365

330

405

345

120

425

383

449

405

402

410

370

460

389

150

488

437

516

462

463

445

405

510

435

185

557

496

587

524

529

485

440

580

490

240

656

579

689

612

625

550

500

670

560

300

755

662

792

700

720

610

550

750

630

400

853

717

899

767

815

640

580

830

700

500

962

791

1016

851

918

690

620

910

770

630

1082

861

1146

935

1027

750

670

1000

840

800

1170

904

1246

987

1119

828

735

1117

931

1000

1261

961

1345

1055

1214

919

811

1254

1038

Voltage Drop (Per Amp Per Meter)

 

 

Conductor cross-section
alarea

 2 cablesd.c.

2 cablessingle-phase a.c.

 3 or 4 cables
three-phase a.c.

2 cables
single
phasea.c.

3 or 4 cables,
3-phase a.c.touching

Reference Method 1

&

11 (touching)

Reference Method1,

11

& 12 (intrefoil
touching)

Reference Method1&11

(Flat
touching)

 

In
ducts

 

In
ground

 

In ducts

 

In ground

1

2

3

4

5

6

7

8

9

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

 

 

r

x

z

r

x

z

r

x

z

 

 

 

 

70

0.67

0.68

0.20

0.71

0.59

0.17

0.62

0.6

0.25

0.65

0.80

0.70

0.70

0.61

95

0.49

0.51

0.195

0.55

0.44

0.17

0.47

0.46

0.24

0.52

0.65

0.53

0.56

0.46

120

0.39

0.41

0.190

0.45

0.35

0.165

0.39

0.38

0.24

0.44

0.55

0.43

0.48

0.37

150

0.31

0.33

0.185

0.38

0.29

0.160

0.33

0.31

0.23

0.39

0.50

0.37

0.43

0.32

185

0.25

0.27

0.185

0.33

0.23

0.160

0.28

0.26

0.23

0.34

0.45

0.31

0.39

0.27

240

0.195

0.21

0.180

0.28

0.18

0.155

0.24

0.21

0.22

0.30

0.40

0.26

0.35

0.23

300

0.155

0.17

0.175

0.25

0.145

0.150

0.21

0.17

0.22

0.28

0.37

0.24

0.32

0.21

400

0.115

0.145

0.170

0.22

0.125

0.150

0.195

0.160

0.21

0.27

0.35

0.21

0.30

0.19

500

0.093

0.125

0.170

0.21

0.105

0.145

0.180

0.145

0.20

0.25

0.33

0.20

0.28

0.18

630

0.073

0.105

0.165

0.195

0.092

0.145

0.170

0.135

0.195

0.24

0.30

0.19

0.26

0.17

800

0.056

0.090

0.160

0.190

0.086

0.140

0.165

0.130

0.180

0.23

0.28

0.18

0.24

0.16

1000

0.045

0.092

0.155

0.180

0.080

0.135

0.155

0.125

0.170

0.21

0.26

0.17

0.22

0.15

Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance